1 Por qué deberíamos Ensayar los Cables de M.T. a Muy Bajas Frecuencias (VLF)? por Martin Baur BAUR Prüf- und Messtechnik GmbH, Sulz/Austria, Director Traducido y Revisado por José Luis Ferreres Nos, Ing. Industrial de Martin Baur, S.A. / Barcelona Abstracts Inspection and commissioning of newly installed HV equipment, especially for the power transmission distribution network, is an important procedure in the reliability and performance of the power supply. Since many years HV DC and HV AC testing at power frequency under laboratory and field conditions have been reliable tools for insulation assessment. Beyond recent development in the international standards, new methods and testing frequencies were added to these new standards like VLF rather than power frequency. The assessment of ageing and preventing damages of medium and high voltage underground cable system is highly important for the utilities today. Due to the quality of the power distribution network and the high cost of increasing demand of reliability in the power supply, the underground cable system needs more performance testing and control.. KEY WORDS: AFTER LAYING TEST, AGING, UNDERGROUND CABLE, CABLE TESTING, CABLE DIAGNOSTICS, CABLE REPLACEMENT, LOSS FACTOR MEASUREMENT, PARTIAL DISCHARGE TESTING AND FAULT LOCATION, URD, VLF TEST. Resúmen La inspección y puesta en servicio de equipos de alta tensión nuevos, especialmente en las redes de distribución y transporte es un proceso muy importante para la fiabilidad y el comportamiento del sistema de alimentación. Desde hace muchos años se han efectuado ensayos de alta tensión en c.c. y en c.a. a la frecuencia industrial tanto en laboratorio como en campo viéndose que ambos sistemas son herramientas fiables para determinar el estado del aislamiento. El desarrollo reciente de las reglamentaciones internacionales, nuevos métodos y nuevas frecuencias de ensayo se han añadido en estas nuevas normas, como la técnica VLF que sustituye cada vez más a la frecuencia industrial. El resultado de un ensayo dieléctrico con tensión alterna y continua para inspección o con el propósito de mantenimiento quedan restringidos a la determinación pasa o no pasa. Un ensayo con la medida del factor de pérdidas a 0,1 Hz puede fácilmente añadirse a un equipo de ensayo VLF para poder diferenciar la condición de envejecimiento de los equipos eléctricos a niveles de ensayo de alta tensión. La evaluación del envejecimiento y la prevención de daños en los sistemas subterráneos de cables de media y alta tensión constituyen una herramienta de la más alta importancia para las compañías eléctricas hoy en día. La calidad de la red de distribución de potencia y los elevados costes de la creciente demanda en la fiabilidad de los sistemas de suministro precisan una atención cuidadosa a fin de controlar las inversiones necesarias para la prevención de fallos durante el servicio. PALABRAS CLAVE: CABLES SUBTERRÁNEOS, ENVEJECIMIENTO, URD, ENSAYO DE CABLES, DIAGNÓSTICO DE CABLES, SUSTITUCIÓN DE CABLES, ENSAYO DESPUÉS DEL TENDIDO, ENSAYO VLF, MEDIDA DEL FACTOR DE PÉRDIDAS, ENSAYO DE DESCARGAS PARCIALES Y LOCALIZACIÓN DE FALTAS. Resume A inspeção e a colocação em funcionamento de equipamento HV recém instalado, especialmente para a rede de distribuição e transmissão de força, é procedimento importante para a segurança e desempenho do fornecimento de energia. Já há muitos anos está provado que testes HV DC e HV AC na freqüência industrial em condições de laboratório ou de campo são ferramentas confiáveis na avaliação do isolamento. Desenvolvimentos recentes nos padrões internacionais, novos métodos e freqüências de testes somaram-se a esses novos padrões, como VLF ao invés de freqüência industrial. A um sistema de testes de Alta Tensão a 0.1 Hz, medição de fator de potência ou de tangente delta pode ser facilmente adicionada ao sistema de teste VLF para determinar a condição de envelhecimento do equipamento elétrico aos níveis de HV. A avaliação de defeitos decorrentes de envelhecimento e a prevenção do sistema de cabos subterrâneos de média e alta tensão atualmente são de fundamental importância para as empresas públicas investimentos necessários para a prevenção de falhas operacionais. PALAVRAS-CHAVE: AFTER LAYING TEST, CABO SUBTERRÃNEO, DE CABOS, DIAGNÓSTICO EM CABOS, ENVELHECIMENTO, DE CABOS, MEDIÇAO DE FATOR DE POTÊNCIA, SUBSTITUIÇÃO TESTE VLF, TESTE, TESTE DE DESCARGA PARCIAL E LOCALIZAÇAO DE DEFEITOS, URD,. 1. Revisión de las normas para ensayo de campo de los cables de AT. A mediados de los 80 se presentaron los métodos de ensayo de campo alternativos para los cables subterráneos de media tensión con aislamiento seco utilizando muy bajas frecuencias en el rango de 0,01 a 1 Hz [1,2]. A parte de la frecuencia industrial también puede utilizarse en los ensayos de campo en c.a., el ensayo VLF. Ensayos de larga duración efectuados tanto en campo como en laboratorio, han demostrado claramente lo práctico y ventajoso del uso del nuevo método de ensayo VLF. La forma de onda de tensión más común en técnica VLF es la senoidal de acuerdo con la norma IEC [3]. En 1996 el CENELEC dentro de su comité de armonización europea publicó la nueva norma HD620 S1 de ensayos de campo para cables de media tensión en el rango de 6 KV a 36 KV [4]. En el año 2004 la IEEE publicó una nueva norma, la IEE Std para el ensayo de campo VLF en cables de media tensión [5]. Los niveles de tensión de ensayo fueron objeto de controversia entre los usuarios y suministradores debido al desconocimiento del nivel de envejecimiento del aislamiento del cable y los posibles daños y degradación que pudiera producirse en el aislamiento del propio cable. Es por tanto recomendable utilizar los valores fijados por esta norma solamente para las puestas en marcha y ensayos después del tendido. 2. Comparación entre los ensayos a frecuencia industrial y con tensión VLF

2 2.1 Comportamiento de las descargas parciales a 0,1 Hz y a 50 Hz Las características comparativas de las PD que aparecen en la figura 1 muestran que la técnica VLF a 0,1 Hz es de lo más comparable con el ensayo de 50 Hz, excepto para la onda VLF cos rectangular en que tanto el nivel como la cadencia, difieren [8] Fig. 3: Fig. 4: Forma característica de Forma característica de la distribución de PDs a la distribución de PDs a 0,1 Hz [8] 50 Hz [8] Fig. 1: Niveles y cadencia de PD con forma de onda senoidal VLF de 0,1 Hz, frecuencia industrial de 50 Hz y cos rectangular de 0,1 Hz. En las figuras 2 a 5 se presentan resultados de formas de onda senoidal. Se puede ver que los resultados de la tensión de incepción (PDIV) son muy similares. La variación en todos los casos es de un valor inferior al 10%, excepto una típica característica de falta que muestra un 30% de PDIV (Tensión de Incepción de las Descargas Parciales) con VLF [7,19]. Como puede verse, también a niveles de tensiones más elevadas hasta 80 KV la tensión VLF muestra resultados comparativos. Las figuras 3 y 4 confirman características de PD muy similares a tensiones mayores en diferentes faltas artificiales ejecutadas en empalmes en un cable de aislamiento de XLPE de 110 KV [8,9,10]. Fig. 2: Comparación de la tensión de incepción de descargas parciales con una fuente de AT con frecuencias de 0,1 Hz y 50 Hz [8] Fig. 5: Tensión de incepción de PDs en un cable de aislamiento XLPE de 110 KV [9,10] 2.2 Factor de disipación VLF en comparación con el factor de disipación (tan delta) a frecuencia industrial Debido al efecto del tiempo de despolarización, las arborescencias de agua en los dieléctricos sólidos son más sensibles al factor de disipación utilizando bajas frecuencias. Con el fin de clasificar los aislamientos como buenos, medio o severamente envejecidos por la presencia de arborescencias de agua, es más efectivo el uso de la frecuencia VLF que el uso de la frecuencia industrial de 50 Hz o las frecuencias variables [11,12,13,16]. Las simulaciones del factor de pérdidas utilizando correlaciones matemáticas, esto es, utilizando el factor de amortiguamiento de una onda oscilante dependen totalmente de la longitud de la fase del cable medido. Además la tangente delta y la variación de la tangente delta en subidas y bajadas progresivas pueden proporcionar una respuesta muy detallada acerca de la presencia de agua en los empalmes y botellas terminales [14]. El usuario debe asegurarse partiendo de una base de datos consistente y fiable, especialmente cuando se usan criterios estrictos que lleven asociados costes significativos de mantenimiento y la determinación precisa de cuando efectuarlo. Los procesos de calibración y validación deben manejarse con cuidado; las decisiones erróneas en los ensayos de campo pueden resultar muy costosas.. 3. Por qué debemos utilizar tensión VLF? Existen varias razones que justifican la ventaja de utilizar VLF en los tendidos de cables subterráneos

3 3.1 Requisitos de seguridad y normativa Nuevas Normas como IEC Mantenimiento basado en el estado real del cable-, definen la fuente de tensión VLF como una forma de onda adecuada para ensayos de alta tensión en campo; esta tensión representa el más moderno estado de la técnica y la práctica actual entre diferentes fuentes de alta tensión. De hecho los ensayo de campo de cables en VLF, basados en las normas anteriores se han convertido en un método universalmente aceptado para las puestas en marcha y trabajos de mantenimiento en las redes de cables de media y alta tensión. Además las normas citadas son poco exigentes. Los operadores pueden escoger libremente niveles más altos con criterios más estrictos de lo que dicen las normas IEC , IEEE o VDE HD S1. Las especificaciones de acuerdo con las normas pretenden y motivan a los suministradores y los usuarios de redes de distribución subterránea a mejorar la fiabilidad del sistema. El control basado en el diagnóstico regular de los cables protege al usuario final de las faltas incipientes antes de que se produzcan tales faltas en los sistemas de distribución urbana. Si por causa de las faltas o daños relacionadas se pierde la garantía del proceso de suministro o instalación, el usuario o suministrador quedarán protegidos (asegurados) si la causa del fallo de la red pudo ser analizada, localizada y justificada previamente con un sistema de diagnóstico no destructivo. 3.2 Razones técnicas para utilizar tensión VLF: -Peso y volumen pequeños de los equipos de ensayo -Mayor eficacia a la hora de localizar los defectos -Mayor sensibilidad en la medida de TD y PD comparado con el método de la onda oscilante. -Eficacia del diagnóstico al utilizar una fuente de AT de forma de onda verdaderamente senoidal, truesinus tanto para PD como para TD. -Monitorización de la posición de las faltas durante las puestas en marcha y los ensayos del cable -Menor riesgo de la tensión VLF eficaz en comparación con la tensión continua (al evitar la formación de cargas espaciales en el aislamiento) -Movilidad en los ensayos de campo 3.3 Razones comerciales para utilizar la tensión VLF: En relación a las estrategias de mantenimiento hay que considerar los siguientes hechos: -Menor consumo de potencia (puede originar costes altos) -Mantenimiento basado en una avería de cable (puede originar costes muy altos) -Mantenimiento basado en el estado real del cable (costes bajos) -Coste de reparación y sustitución (costes bajos) 3.4 Razones estratégicas para utilizar tension VLF: -Se mejora globalmente la fiabilidad de la red -Reduce las horas perdidas del usuario por año -Decisiones de sustituciones totales o parciales del cable antes de que éste falle, con el tiempo para planificarlo -Consideraciones acerca de la fiabilidad global del sistema basado en las medidas de campo -Determinación del estado real del sistema tras evaluar los datos medidos en un ensayo de campo 4. Cómo mejorar la fiabilidad de los sistemas urbanos de distribución de cables? 4.1 Ensayo de cubiertas de cable y localización de las fugas de pantalla Para asegurar la calidad a largo plazo de la rigidez dieléctrica del aislamiento de los cables de media y alta tensión deberá ensayarse la pantalla metálica del mismo de acuerdo con la norma IEC con una tensión de 4 KV c.c por milímetro de espesor de la cubierta, contra tierra durante un minuto [3]. La práctica de un control regular del aislamiento de las pantallas, especialmente después del tendido, reduce los posibles daños y garantiza que no haya entrada de humedad ni que se originen problemas de arborescencias de agua. Para prelocalizar las faltas de pantalla en los cables de alta tensión se utiliza un método de localización denominado Método del puente de Murray/Glaser, que proporciona una precisión inferior al 1% en la determinación de la distancia del defecto [15]. 4.2 Factor de Corrosión Para determinar el factor de corrosión, CF, se puede utilizar el puente de Wheastone para calcular la degradación actual de la pantalla metálica exterior [1]. A continuación damos la fórmula en donde Rs representa la resistencia calculada de la longitud total de la pantalla (formada por hilos o cintas metálicas conductoras) dividida por la resistencia longitudinal actual medida Rc, multiplicado por 100. Este coeficiente influye en la precisión de la medida del puente de Murray y tiene también influencia en las medidas de tangente delta [11,15] CF = Rs/Rc*100 [%] (1) 4.3 Ensayos de alta tensión VLF Destinados a asegurar la fiabilidad de la red de distribución a largo plazo y poder ensayar los cables utilizando niveles de alta tensión VLF en campo según recomiendan las normas, detectando y corrigiendo las faltas incipientes de la red [3,4]. Hoy en día existen en el mercado equipos de ensayo VLF portátiles para su uso en campo. Véase por ejemplo el equipo de la figura 6. Las investigaciones más recientes comparando los resultados de los diagnósticos a la frecuencia industrial y los ensayos VLF, muestran una total aceptación del sistema de muy baja frecuencia. Los equipos diseñados

4 recientemente con la última tecnología VLF de alta tensión utilizan amplificadores de estado sólido de alta precisión, una técnica que proporciona señales de salida de verdadero valor eficaz senoidal y permiten las mediciones de tangente delta libres de armónicos y las medidas de precisión en diagnóstico de descargas parciales. [10,11] Fig. 6: Equipo de ensayo portátil VLF, hasta 40 KV pico y 23 KV eficaces ( BAUR) 4.4 Herramientas de diagnóstico VLF Factor disipación (TD) a 0.1 Hz Los métodos de diagnóstico como descargas parciales (PD) y factor de disipación (TD) son métodos de medida recomendados para el control del estado del aislamiento bajo condiciones de campo de estrés eléctrico de alta tensión y basados en las formas de onda de tensión que se adapten a lo indicado por la norma IEC Los ensayos de diagnóstico con tensión de ensayo comenzando a 0,5 Uo hasta un máximo nivel de 2 Uo son práctica habitual hoy en día. El nivel de tensión utilizado debe ser manejado cuidadosamente evitando provocar fallos incipientes especialmente en cables envejecidos por el servicio. Si el estado del aislante del cable es desconocido o se trata de un cable crítico el nivel de tensión aplicada nunca superará los límites superiores recomendados por el usuario o el fabricante del cable. Evitando las posibles perforaciones del aislamiento, el operador puede limitar el nivel de tensión muy por debajo del límite de la rigidez dieléctrica o utilizar el criterio de la pendiente de variación de las pérdidas o el nivel de la tensión de incepción de las descargas parciales Criterios TD en VLF Los criterios recomendados del factor de pérdidas TD> 2.2*10-3 y pendiente de TD< 1*10-3 para cable altamente degradado de aislamiento de XLPE son los más utilizados en la mayoría de los países europeos [5,8,12,13]. En lo que respecta al criterio de los niveles de tangente delta usados en USA se utilizan valores incluso inferiores a los anteriores, basados en investigaciones hechas por un proyecto del gobierno de USA, NEETRAC CDFI y ejecutado por el Instituto de tecnología de Georgia. Las razones pueden encontrarse en el hecho de que allí se dan otras formas de diseño de los cables, métodos distintos de tendido y especialmente lo relacionado con las distintas formulaciones de las mezclas de los materiales poliméricos utilizados, como XLPE, HDXLPE y EPR. Además el diseño del cable de aislamiento EPR con cubierta exterior concéntrica que actúa como neutro puede llevar a incrementar los valores de TD por un factor de 3 a Histéresis en la medida de TD en VLF en la subida y bajada de la tensión de ensayo En 1999 se detectó un nuevo efecto en los ensayos que utilizaban TD VLF, al incrementar la tensión de ensayo con el tiempo, para detectar accesorios mal montados. Brincourt y otros de EDF Francia [20] y NEETRAC [11] pudieron probar claramente que era debido a la entrada de humedad en los empalmes y botellas. El decrecimiento de los valores de TD para tensiones crecientes está causado normalmente por la humedad que se evapora muy rápidamente en el ensayo [11,20]. Como consecuencia, el efecto secado como así se le conoce, puede medirse en tiempo muy corto, normalmente en 1 ó 2 minutos. Si las medidas de TD se utilizan con niveles de tensión crecientes y decrecientes puede confeccionarse una curva de histéresis de TD que está correlacionada con el contenido de humedad del aislamiento. La probabilidad de un empalme mal montado y la entrada de humedad puede comprobarse así de forma fácil. En muchos casos prácticos una medida de TD antes y después de sustituir un empalme puede ayudar a resolver el problema [11,20] Internamente los defectos del cable con humedad embebida en el propio aislamiento del cable muestran un efecto de histéresis muy pequeño o indetectable. Dado que el estrés de larga duración en el aislamiento de los cables de AT degradados por envejecimiento no es apreciable, la compañía BAUR ha introducido una práctica nueva en lo que se refiere en la metodología en el ensayo de histéresis VLF. La histéresis del factor de pérdidas se evalúa utilizando una subida y una bajada de tensión VLF en un solo ensayo, véase la Fig. 7 TD ,5 3 2,5 2 1,5 1 0,5 0 6 kv 12 kv 18 kv 24 kv HV rise HV decay Fig 7: Histéresis del factor de pérdidas TD en VLF con tensión ascendente y descendente

5 Los valores de TD en otros tipos de aislamiento como PILC (cables con aislamiento de papel aceitado con cubierta de plomo), EPR, HD-XLPE y Co-polímeros muestran otros valores de arranque de la TD cuando son nuevos, que varían con el tiempo de instalación, siendo sin embargo con el tiempo en servicio, muy similares a los aislamientos XLPE. Los niveles que se utilizan como criterio individual para cada tipo de aislamiento y la comparación de las medidas de TD entre las tres fases son herramientas muy valiosas para la calificación del estado del cable Medida de descargas parciales con VLF y otras formas de onda de tensión de prueba El mapeado de la posición de las descargas parciales en campo se ha venido llevando a cabo como práctica habitual desde hace más de 10 años. En el año 2007 se ha efectuado un ensayo de laboratorio con diferentes formas de onda de tensión para ensayos en AT en varios tipos de defectos artificiales en RWE EUROTEST en Alemania, que muestra resultados no uniformes [19]. Las interpretaciones de la magnitud de las descargas parciales y los resultados cuantitativos no son comparables [9]. Los usuarios no disponen de reglas de conocimiento para cuantificar el nivel para diferentes tipos de defectos. La magnitud no es sinónimo de daño severo o de una situación menos peligrosa en el aislamiento del cable. Normalmente no es posible predecir posibles fallos si los cables no se prueban hasta la tensión de perforación. Los defectos singulares son fácilmente localizados utilizando técnicas de ecometría. La magnitud de las PD no está siempre correlacionada con el defecto más alto o más peligroso dado que el tipo de defecto es generalmente desconocido. A veces la densidad de PD s en una misma posición del mapa de puntos y la cadencia o repetibilidad son más informativas de su peligrosidad potencial que la propia magnitud. Únicamente los datos históricos pueden llevar a tomar mejores decisiones en lo que respecta a la sustitución de un cable o a su reparación. Fig. 8: Equipo portátil detector de PDs y localización de los puntos de las PDs en ensayos de campo ( BAUR) 5. Consideraciones a cerca del tiempo de vida de un cable Hoy en día los cálculos del tiempo estimado de la duración residual de un cable en servicio basados en los criterios de las medidas simples de TD o PD no son posibles todavía. Solamente las observaciones de larga duración y los datos históricos y la evaluación comparativa de estos, en una base de datos de los ensayos individuales ayudan a determinar este tiempo. Decisiones útiles acerca de cuando sustituir un cable o empalme o llevar a cabo una reparación pueden tomarse de forma segura basándonos en los valores de tangente delta y el mapeado de las medidas de PD obtenidos con las medidas de diagnóstico [17,18] 6. Conclusión El ensayo de cables VLF en campo se ha convertido en una práctica universal en todo el mundo para la puesta en marcha y el mantenimiento de redes de cables de media y alta tensión, debido a la disponibilidad en el mercado de equipos pequeños y portátiles VLF. Las ventajas iniciales del ensayo tradicional en corriente continua, portabilidad y precio de los ensayadores, han sido superadas hoy en día por la economía y las ventajas técnicas del ensayo en VLF. Varias normas nuevas nacionales e internacionales han sido publicadas en todo el mundo como guías teóricas y prácticas de uso de estos equipos. Las más recientes investigaciones para transferir esta tecnología al ensayo de redes de transporte de alta y muy alta tensión avalan el uso de esta técnica. Las herramientas combinadas de diagnóstico TD y PD basadas en la tensión Truesinus VLF permiten localizar prematuramente los defectos en los cables antes de que estos se conviertan en averías. Una estrategia preventiva de mantenimiento combinada con un método de análisis estadístico es la mejor forma de mejorar la fiabilidad del sistema de cables de distribución. La determinación de la calidad del cable en una red de distribución con un plan prematuro y preprogramado de reparaciones, sustitución parcial o sustitución completa de un determinado cable dentro de la red de distribución incrementa el comportamiento y la fiabilidad de dicho sistema y permite estimar basándonos en los datos reales la posible duración en servicio de un determinado cable.

6 7. Referencias [1] M. Krüger, R. Feurstein, A. Filz, "Very Low Frequency Methods for Testing New Cables", IEEE Int. Symposium on Electrical Insulation, Toronto, June 1990, pp [2] O. Goll, " 0.1 Hz VLF cable testing and diagnostics in utility networks; principle and field experience 9th ISH No , Graz, Austria, 1995 [3] IEC Standards IEC , International Electrotechnical Commission, High Voltage Field Testing, IEC Central Office 3, rue de Varembé, P.O. Box 131, CH GENEVA 20, Switzerland, DIN VDE Standard /A2, Edition: Starkstromkabel Teil 620 Energieverteilungskabel mit extrudierter Isolierung für Nennspannungen 3,6/6 (7,2) kv bis 20,8/36 (42) kv; Änderung A2 [4] CENELEC Standard, Harmonization Document HD 620 S1 and HD 621 S1 Test after Installation Requirement for Medium High Voltage Cables with PE (Section 5C-1) and PVC (5C-2) shield, Part 5 : 1996, Brussels. [5] IEEE, 2005, IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF), IEEE Std , New York, United States [6] S. C. MOH, "Very low Frequency Testing -Its Effectiveness in Detecting Hidden Defects in Cables", CIRED 2003Barcelona,, Paper 84 [7] R. Bach, W. Kalkner, "Comparison of different voltage types for evaluation of layed medium voltage cables", 8th Int. Symposium on High Voltage Engineering, Yokohama 1993, paper [8] D. Pepper, K. Rethmeier, W. Kalkner, PD testing of service aged joints in XLPE insulated MV cables at test voltages with variable shape and frequency, XIIIth International Symposium on HV Engineering, Netherlands 2003, SMIT Milpress Edition ISBN [9] K. Rethmeir, Applicability of sinusoidal VLF voltage for PD diagnostic measurements, Research study on a 110 KV XLPE cable at the HV at the HV Institute Technical University Berlin: CIGRE 2006 Session B , Paris, 27 August-01 September [10] P. Mohaupt, W. Kalkner, Bergmann, New Approach for HV Cable On-Site Testing, CIRED 2007, paper A 4.6 [11]J. Hernandez, N. Hampton, R. Harley, R. Hartlein, Practical Issues Regarding the Use of Dielectric Measurements to Diagnose the Service Health of MV Cables, Georgia Institute of Technology (NEETRAC), JICABLE 2007, paper A 7.5 [12]R. Bach, W. Kalkner, H. Oldehoff, "Verlustfaktormessung bei 0.1 Hz an betriebsgealterten PE/VPE - Kabelanlagen", Sonderdruck No aus Elektrizitätswirtschaft, VDEW, Jg.92, 1993, S [13]M. Kuschel, R. Plath, W. Kalkner, "Dissipation Factor Measurement at 0.1 Hz as a Diagnostic Tool for Service-aged XLPE - insulated Medium High Voltage Cables",.9th ISH Symposium, 1995, Graz, paper [14]T. Espilit, Contribution of the diagnosis in real conditions of operations, EDF Renadière, France, Department Laboratory of Electrical Materials, November 2005 [15]M. Krüger, Prelocation of Cable Sheath Faults, Technical Report No. 8508e-1985, Baur Prüf- und Messtechnik 6832 Sulz, Austria, 1985 [16]T. Espilit, F. Zorzi, V. Regaudie, C. Gaudin, R. Tambrun, Diagnostic for Paper Cable Condition Assessment, EDF R&D France, JICABLE 2007, paper A 5.4 [17]A. Rakowska, Service Experiences for MV Cable Network Optimistic or Pessimistic State of the Art, Poznan University of Technology, Poland, JICABLE 2007, paper B2.5 [18]R. Jongen, P. Morshuis, J. J. Smit, A. L. J. Janssen, E. Gulski, Failure Prediction in 50 kv Massimpregnated Power Cable Systems, JICABLE 2007, paper A 6.3 [19]Dirk Borneburg, Ingo Diefenbach, Frank Merschel, Mono Kliesch, Martin Keller, Dirk Rittinghaus, Vergleich verfügbarer Messverfahren zur Überprüfung der Einschaltbereitschaft von VPE- MS-Kabeln Elektrizitätswirtschaft Jg. 106 (2007) Heft 4. [20]T. BRINCOURT, V. REGAUDIE: Evaluation of different diagnostic methods for the french underground MV network, EDF DER, Moret sur Loing, France, JICABLE 1999 Autor Martin A. Baur, Director BAUR Prüf- und Messtechnik GmbH Raiffeisenstrasse Sulz/Austria : Traducción y adaptación José Luis Ferreres Nos, Ing. Industrial, Martin Baur, S.A. Plza : Eguilaz 8 bis Barcelona/España : Observaciones truesinus es una marca internacional registrada por BAUR Prüf- und Messtechnik GmbH, Sulz/Austria

DIAGNOSTICO DE CABLES DE ALTA TENSION (132KV / 220KV) ENSAYOS DE VERY LOW FREQUENCY (VLF) - DESCARGAS PARCIALES Y TANGENTE DELTA IN-SITU.

DIAGNOSTICO DE CABLES DE ALTA TENSION (132KV / 220KV) ENSAYOS DE VERY LOW FREQUENCY (VLF) - DESCARGAS PARCIALES Y TANGENTE DELTA IN-SITU. DIAGNOSTICO DE CABLES DE ALTA TENSION (132KV / 220KV) ENSAYOS DE VERY LOW FREQUENCY (VLF) - DESCARGAS PARCIALES Y TANGENTE DELTA IN-SITU. HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH VLF+PD+TD

Más detalles

Ensayos VLF (muy baja frecuencia) para cables de Media Tensión

Ensayos VLF (muy baja frecuencia) para cables de Media Tensión Ensayos VLF (muy baja frecuencia) para cables de Media Tensión Domingo Oliva Rodero Técnico comercial unitronics electric doliva@unitronics-electric.com www.unitronics-electric.es Introducción La fiabilidad

Más detalles

ENSAYO DE LAS CUBIERTAS DE LOS CABLES NUEVOS DE AISLAMIENTO SECO DE M.T. DESPUÉS DEL TENDIDO

ENSAYO DE LAS CUBIERTAS DE LOS CABLES NUEVOS DE AISLAMIENTO SECO DE M.T. DESPUÉS DEL TENDIDO ENSAYO DE LAS CUBIERTAS DE LOS CABLES NUEVOS DE AISLAMIENTO SECO DE M.T. DESPUÉS DEL TENDIDO Jose Luis Ferreres Martin Baur, S.A. / Barcelona Resumen La importancia creciente de la seguridad de los cables

Más detalles

LAS DESCARGAS PARCIALES EN CABLES DE ENERGIA

LAS DESCARGAS PARCIALES EN CABLES DE ENERGIA LAS DESCARGAS PARCIALES EN CABLES DE ENERGIA UN LENTO PERO EFECTIVO ENEMIGO INTERNO (ParteII) INTRODUCCION: Es sabido que la presencia de descargas parciales en cables de media y alta tensión, constituyen

Más detalles

Ensayo de cables y diagnóstico BAUR. Las redes son delicadas. Nosotros le ayudamos a protegerlas.

Ensayo de cables y diagnóstico BAUR. Las redes son delicadas. Nosotros le ayudamos a protegerlas. Ensayo de cables y diagnóstico BAUR Las redes son delicadas. Nosotros le ayudamos a protegerlas. Mejoramos la seguridad y rentabilidad de las redes de cables. Ensayo y diagnóstico de alta tensión con BAUR.

Más detalles

Historia de Cables. Tipos de fallas en cables subterráneos. Pasos para la localización de fallas

Historia de Cables. Tipos de fallas en cables subterráneos. Pasos para la localización de fallas Historia de Cables Tipos de fallas en cables subterráneos Pasos para la localización de fallas Disertante: Ing. Damian Lopez Gentile Historia de Cables Historia Cables de Potencia (aislación de papel)

Más detalles

Diagnósticos de cables subterráneos de Media Tensión de Distribución: primera experiencia en UTE

Diagnósticos de cables subterráneos de Media Tensión de Distribución: primera experiencia en UTE 1 Diagnósticos de cables subterráneos de Media Tensión de Distribución: primera experiencia en UTE Ing. Electr. Daniel Scanagatta, U.T.E Resumen Este trabajo describe la primera experiencia de diagnostico

Más detalles

El único equipo combinado para comprobación y diagnóstico de cables

El único equipo combinado para comprobación y diagnóstico de cables El único equipo combinado para comprobación y diagnóstico de cables DAC 0,1 Hz senoidal 0,1 Hz CR TDS NT Dos formas de tensión acreditadas en un solo dispositivo Permite la comprobación normalizada de

Más detalles

A2-81 EXPERIENCIAS EN DIAGNÓSTICO DE AISLAMIENTO ACEITE-PAPEL CON ESPECTROSCOPIA DIELÉCTRICA EN EL DOMINIO DE LA FRECUENCIA

A2-81 EXPERIENCIAS EN DIAGNÓSTICO DE AISLAMIENTO ACEITE-PAPEL CON ESPECTROSCOPIA DIELÉCTRICA EN EL DOMINIO DE LA FRECUENCIA III CONGRESO VENEZOLANO DE REDES Y ENERGÍA ELÉCTRICA Comité Nacional Venezolano Marzo 202 A2-8 EXPERIENCIAS EN DIAGNÓSTICO DE AISLAMIENTO ACEITE-PAPEL CON ESPECTROSCOPIA DIELÉCTRICA EN EL DOMINIO DE LA

Más detalles

Cables monopolares media tensión aislados 90 ºC Monopolar insulated medium voltage cables 90 ºC

Cables monopolares media tensión aislados 90 ºC Monopolar insulated medium voltage cables 90 ºC Cables monopolares media tensión aislados 90 ºC Monopolar insulated medium voltage cables 90 ºC Nivel de aislamiento 100 y 133%, pantalla cinta de cobre, 5 kv a 46 kv 100 and 133% level, copper tape shield,

Más detalles

PROGRAMAS DE GESTIÓN DE VIDA DE CABLES EN CNA Y CNT

PROGRAMAS DE GESTIÓN DE VIDA DE CABLES EN CNA Y CNT PROGRAMAS DE GESTIÓN DE VIDA DE CABLES EN CNA Y CNT PROGRAMAS DE GESTIÓN DE VIDA DE CABLES EN CNA Y CNT PROGRAMAS APLICADOS: Vigilancia del aislamiento de cables eléctricos (AMP XI.E1 - Nureg 1801) Vigilancia

Más detalles

ENSAYOS DE DESCARGAS PARCIALES IN-SITU, EN CABLES DE DISTRIBUCION Y POTENCIA

ENSAYOS DE DESCARGAS PARCIALES IN-SITU, EN CABLES DE DISTRIBUCION Y POTENCIA ENSAYOS DE DESCARGAS PARCIALES IN-SITU, EN CABLES DE DISTRIBUCION Y POTENCIA INEFICIENCIA DE LA TECNICA DE ONDAS OSCILANTES AMORTIGUADAS (OSW Oscillanting Wave Testing - DAC: Damped Alternating Voltage)

Más detalles

Cirprotec Gama ISO-Check

Cirprotec Gama ISO-Check 01 Cirprotec Gama ISO-Check Vigilantes de aislamiento Nuevo Protección de personas e instalaciones contra el fallo de aislamiento ISO-Check Seguridad y continuidad de servicio Las redes de suministro aisladas

Más detalles

Monitoreo en línea de transformadores de potencia utilizando sensores de campo cercano

Monitoreo en línea de transformadores de potencia utilizando sensores de campo cercano COMITÉ MEXICANO 12-02 BIENAL 2001 Monitoreo en línea de transformadores de potencia utilizando sensores de campo cercano V.R. García-Colón J.T. Ramirez-Niño Ing. L. Gómez H. IEEE Member gcolon@iie.org.mx

Más detalles

Ingeniería Energética E-ISSN: 1815-5901 orestes@cipel.ispjae.edu.cu. Instituto Superior Politécnico José Antonio Echeverría. Cuba

Ingeniería Energética E-ISSN: 1815-5901 orestes@cipel.ispjae.edu.cu. Instituto Superior Politécnico José Antonio Echeverría. Cuba Ingeniería Energética E-ISSN: 1815-5901 orestes@cipel.ispjae.edu.cu Instituto Superior Politécnico José Antonio Echeverría Cuba Martínez, José A.; Ugarte, Roberto; Hernández, Gualfrido; Ramírez, Miguel

Más detalles

Spanish Experience in PD Measurements on HV Cables Installed in Electrical Grids

Spanish Experience in PD Measurements on HV Cables Installed in Electrical Grids Spanish Experience in PD Measurements on HV Cables Installed in Electrical Grids Fernando Álvarez Gómez Experiencias en España en la medida de descargas parciales en cables de alta tensión instalados en

Más detalles

REGLAMENTO : SEGURIDAD DE INSTALACIONES DESTINADAS A LA PRODUCCIÓN, TRANSFORMACIÓN, TRANSPORTE Y DISTRIBUCIÓN DE ENERGÍA ELÉCTRICA.

REGLAMENTO : SEGURIDAD DE INSTALACIONES DESTINADAS A LA PRODUCCIÓN, TRANSFORMACIÓN, TRANSPORTE Y DISTRIBUCIÓN DE ENERGÍA ELÉCTRICA. DIVISIÓN DE INGENIERÍA DE ELECTRICIDAD PLIEGO TÉCNICO NORMATIVO : RPTD N 5. MATERIA : AISLACIÓN. REGLAMENTO : SEGURIDAD DE INSTALACIONES DESTINADAS A LA PRODUCCIÓN, TRANSFORMACIÓN, TRANSPORTE Y DISTRIBUCIÓN

Más detalles

NORMAS DE MATERIALES PARA REDES AÉREAS. AISLADORES POLIMÉRICOS TIPO PIN PARA 13.2 kv y 44 kv

NORMAS DE MATERIALES PARA REDES AÉREAS. AISLADORES POLIMÉRICOS TIPO PIN PARA 13.2 kv y 44 kv NORMAS DE MATERIALES PARA AÉREAS 1. ALCANCE Estas especificaciones cubren los requerimientos y ensayos de los aisladores tipo pin polimérico para ser usados con cable cubierto y conductor desnudo en las

Más detalles

ENSAYO DE DESCARGAS PARCIALES EN TRANSFORMADORES Preparado para: CRE - BOLIVIA

ENSAYO DE DESCARGAS PARCIALES EN TRANSFORMADORES Preparado para: CRE - BOLIVIA página 1 de 11 1. PROPOSITO Y ALCANCE: Establecer un método o procedimiento de medición de descargas parciales en transformadores de media y alta tensión; utilizando el detector ICM Compact, de acuerdo

Más detalles

Laboratorio de Análisis para la Industria Energética. Pablo Molina Delegado Comercial

Laboratorio de Análisis para la Industria Energética. Pablo Molina Delegado Comercial Laboratorio de Análisis para la Industria Energética Pablo Molina Delegado Comercial Quiénes Somos? TJ H 2 b Analytical Services Especializados en análisis de materiales aislantes y en el diagnóstico de

Más detalles

Código: (IT.0100.ES.RE.EIC)

Código: (IT.0100.ES.RE.EIC) instrucción Especificaciones Particulares para Instalaciones de Conexión. Medidas y Ensayos en Líneas Eléctricas Subterráneas antes de su puesta Código: (IT.0100.ES.RE.EIC) Edición: (3) Elaborado Revisado

Más detalles

PÉRDIDAS EN LOS DIELECTRICOS - 3º Parte Página 1 de 9

PÉRDIDAS EN LOS DIELECTRICOS - 3º Parte Página 1 de 9 PÉRDIDAS EN LOS DIELECTRICOS - 3º Parte Página 1 de 9 6. Uso de la tangente delta para la evaluación y/o seguimiento del estado de los aislamientos. La medición de la tangente delta se encuentra aplicada

Más detalles

Pruebas Eléctricas para Puesta en Marcha y Mantenimiento de Transformadores ARGENTINA JULIO 2010

Pruebas Eléctricas para Puesta en Marcha y Mantenimiento de Transformadores ARGENTINA JULIO 2010 Pruebas Eléctricas para Puesta en Marcha y Mantenimiento de Transformadores ARGENTINA JULIO 2010 1 Necesidad de Pruebas Evitar Fallas Pocos son los transformadores que fallan por envejecimiento y fin de

Más detalles

Megger Megger Megger Megger Megger

Megger Megger Megger Megger Megger Optimización del Mantenimiento de Transformadores con Diagnóstico Avanzado del Aislamiento Envíenos sus preguntas y comentarios Respuesta Dieléctrica en el Dominio de Frecuencia Seminario Preguntas y Comentarios

Más detalles

UNIVERSIDAD TECNOLOGICA NACIONAL FACULTAD REGIONAL AVELLANEDA GUIA DE LABORATORIO UTNLAT

UNIVERSIDAD TECNOLOGICA NACIONAL FACULTAD REGIONAL AVELLANEDA GUIA DE LABORATORIO UTNLAT PE-01 a PE-08 UNIVERSIDAD TECNOLOGICA NACIONAL FACULTAD REGIONAL AVELLANEDA GUIA DE LABORATORIO PRACTICAS DE ENSAYOS EN EL TEMA: TRANSFORMADORES DE DISTRIBUCION Y POTENCIA - ENSAYOS EN CAMPO - PARTE I

Más detalles

Soluciones de monitoreo de OMICRON

Soluciones de monitoreo de OMICRON Soluciones de monitoreo de OMICRON Monitoreo de descargas parciales de activos de alta tensión M/G Prolongación de la vida de servicio de los activos de alta tensión Por qué monitorear? La degradación

Más detalles

Sistemas de ensayo de SebaKMT. Evite el estrés de los ensayos! SebaKMT tiene las respuestas adecuadas: seguridad, rapidez y rentabilidad.

Sistemas de ensayo de SebaKMT. Evite el estrés de los ensayos! SebaKMT tiene las respuestas adecuadas: seguridad, rapidez y rentabilidad. Sistemas de ensayo de SebaKMT Evite el estrés de los ensayos! SebaKMT tiene las respuestas adecuadas: seguridad, rapidez y rentabilidad. Saber qué hacer. Y cómo conseguirlo. Ensayar primero significa ahorrar

Más detalles

Subestaciones eléctricas encapsuladas (GIS) Francis Rodríguez, Ing. MBA

Subestaciones eléctricas encapsuladas (GIS) Francis Rodríguez, Ing. MBA Subestaciones eléctricas encapsuladas (GIS), Ing. MBA 7 y 8 marzo, 2013 2 Agenda Tendencias Componentes típicos Ventajas y desventajas Configuraciones típicas Subestaciones móviles Normas y pruebas típicas

Más detalles

www.saferinstrument.com

www.saferinstrument.com www.saferinstrument.com Conectamos nuestros recursos con tus necesidades Somos una ingeniería que proporciona soluciones y servicios enmarcados en el ámbito de la instrumentación eléctrica y electrónica,

Más detalles

9.1 DIELÉCTRICOS 9.1.1 QUÉ SON LOS DIELÉCTRICOS? 9.1.2 RIGIDEZ DIELÉCTRICA

9.1 DIELÉCTRICOS 9.1.1 QUÉ SON LOS DIELÉCTRICOS? 9.1.2 RIGIDEZ DIELÉCTRICA 9 DIELÉCTRICOS 9.1 DIELÉCTRICOS 9.1.1 QUÉ SON LOS DIELÉCTRICOS? Los dieléctricos son materiales, generalmente no metálicos, con una alta resistividad, por lo que la circulación de corriente a través de

Más detalles

UNIVERSIDAD TECNOLOGICA NACIONAL FACULTAD REGIONAL AVELLANEDA GUIA DE LABORATORIO UTNLAT

UNIVERSIDAD TECNOLOGICA NACIONAL FACULTAD REGIONAL AVELLANEDA GUIA DE LABORATORIO UTNLAT PE-01 a PE-08 UNIVERSIDAD TECNOLOGICA NACIONAL FACULTAD REGIONAL AVELLANEDA GUIA DE LABORATORIO PRACTICAS DE ENSAYOS EN EL TEMA: TRANSFORMADORES DE DISTRIBUCION Y POTENCIA - ENSAYOS EN CAMPO - PARTE I

Más detalles

Sistemas de monitorización online del aceite para transformadores de potencia de Centrales Nucleares

Sistemas de monitorización online del aceite para transformadores de potencia de Centrales Nucleares Sistemas de monitorización online del aceite para transformadores de potencia de Centrales Nucleares Sabela Sarandeses Empresarios Agrupados ssy@empre.es Resumen Las Centrales Nucleares están mostrando

Más detalles

Las tres tensiones nominales (U o

Las tres tensiones nominales (U o Las tres tensiones nominales (U o, U, U m de un cable de alta tensión (U o mayor a 1 kv, 50 Hz y los factores de fallas a tierra de la red según las normativas argentina e internacional Por Ing. Juan Carlos

Más detalles

Factores de corrección de los rangos eléctricos para tableros de media tensión aislados en aire por altitud de operación

Factores de corrección de los rangos eléctricos para tableros de media tensión aislados en aire por altitud de operación GE Industrial Solutions Factores de corrección de los rangos eléctricos para tableros de media tensión aislados en aire por altitud de operación - Dany Huamán, Ingeniero de Especificación para Perú Programa

Más detalles

Las redes son delicadas. Nosotros le ayudamos a protegerlas.

Las redes son delicadas. Nosotros le ayudamos a protegerlas. Las redes son delicadas. Nosotros le ayudamos a protegerlas. Quiénes somos Ensuring the flow Contribuimos a la explotación segura y sin averías de redes e instalaciones eléctricas en todo el mundo. Para

Más detalles

Longitud en la que la tensión de pico es 1.15 veces superior a la tensión del bus de continua y r L = 0.8

Longitud en la que la tensión de pico es 1.15 veces superior a la tensión del bus de continua y r L = 0.8 Medidas entre el motor y el variador de velocidad Nota de aplicación Como consecuencia del tendido de cable entre el variador de frecuencia y el motor, pueden presentarse problemas tales como la destrucción

Más detalles

6. Determinación de la sección de los conductores. Consejos para un Cableado Seguro Propiedad de Prysmian, Inc.

6. Determinación de la sección de los conductores. Consejos para un Cableado Seguro Propiedad de Prysmian, Inc. 6. Determinación de la sección de los conductores Características Funcionales de los Cables Las líneas o cables deben ser capaces de transportar la corriente normal de funcionamiento, y la que se presenta

Más detalles

Trazabilidad en la Calibración de Equipos de Electrocirugía

Trazabilidad en la Calibración de Equipos de Electrocirugía 1 Trazabilidad en la Calibración de Equipos de Electrocirugía Ing. German Gomez INTI - Electrónica e Informática, ger@inti.gob.ar Resumen El Vocabulario internacional de Metrología define la trazabilidad

Más detalles

GUIA DE INSTALAÇÃO TC DE FALTA À TERRA SSW7000

GUIA DE INSTALAÇÃO TC DE FALTA À TERRA SSW7000 GUIA DE INSTALAÇÃO TC DE FALTA À TERRA SSW7000 I. DESCRIÇÃO O TC de falta à terra é utilizado para a realização da medição da corrente de falta à terra do circuito trifásico de alimentação do motor. A

Más detalles

Universidad de Cantabria Departamento de Electrónica y Computadores TESIS DOCTORAL

Universidad de Cantabria Departamento de Electrónica y Computadores TESIS DOCTORAL Universidad de Cantabria Departamento de Electrónica y Computadores TESIS DOCTORAL Nuevo Método de Detección y Análisis en Tiempo Real de Eventos en la Tensión de Suministro de Energía Eléctrica Empleando

Más detalles

Consejería de Industria, Turismo, Empresa e Innovación Dirección General de Industria, Energía y Minas. Jornada

Consejería de Industria, Turismo, Empresa e Innovación Dirección General de Industria, Energía y Minas. Jornada Jornada Presentación del del nuevo nuevo Reglamento sobre sobre Condiciones Técnicas y Garantías de de Seguridad en en Instalaciones Eléctricas de de Alta Alta Tensión Consejería de Industria, Turismo,

Más detalles

artículo técnico Qué se entiende como prueba de resistencia Por: Chauvin Arnoux Por qué tener un programa de prueba

artículo técnico Qué se entiende como prueba de resistencia Por: Chauvin Arnoux Por qué tener un programa de prueba Qué se entiende como prueba de resistencia de aislamiento Por: Chauvin Arnoux Por qué tener un programa de prueba del aislamiento? Se recomienda un programa regular para probar la resistencia de aislamiento,

Más detalles

En último lugar, se extraen las conclusiones de este estudio que, a modo de resumen, son:

En último lugar, se extraen las conclusiones de este estudio que, a modo de resumen, son: 1 1. RESUMEN El objetivo de este proyecto es definir gamas de mantenimiento para cables subterráneos de Alta Tensión, basándose en la metodología RCM (Mantenimiento Basado en la Fiabilidad); establecer

Más detalles

INSTALADOR ELECTRICISTA DE EDIFICIOS Y VIVIENDAS

INSTALADOR ELECTRICISTA DE EDIFICIOS Y VIVIENDAS INSTALADOR ELECTRICISTA DE EDIFICIOS Y VIVIENDAS 75101015 Marque con una X el período correspondiente: O 1º PERIODO FORMATIVO Instalaciones de enlace Características y tipos de los elementos Emplazamiento

Más detalles

A2-78. Evaluación de dos metodologías para medir la respuesta en frecuencia de autotransformadores monofásicos

A2-78. Evaluación de dos metodologías para medir la respuesta en frecuencia de autotransformadores monofásicos II CONGRESO VENEZOLANO DE REDES Y ENERGÍA ELÉCTRICA Comité Nacional Venezolano Junio 2009 A2-78 Evaluación de dos metodologías para medir la respuesta en frecuencia de autotransformadores monofásicos R.

Más detalles

NORMAS DE MATERIALES PARA REDES AÉREAS CUBIERTAS PROTECTORAS

NORMAS DE MATERIALES PARA REDES AÉREAS CUBIERTAS PROTECTORAS 1. ALCANCE La norma hace parte del grupo de materiales normalizados y tiene como propósito fundamental determinar todas las características que deberán tener los materiales, dispositivos, herrajes y accesorios

Más detalles

Curso de Electricidad, Electrónica e Instrumentación Biomédica con Seguridad - CEEIBS -

Curso de Electricidad, Electrónica e Instrumentación Biomédica con Seguridad - CEEIBS - Curso de Electricidad, Electrónica e Instrumentación Biomédica con Seguridad - CEEIBS - 1/18 Normas de seguridad eléctrica - Introducción Introducción: La tecnología médica ha aumentado considerablemente

Más detalles

LA EMPRESA SERVICIOS. Reparación. Reparación de maquinaria eléctrica Sustitución de devanados de BT Mecanización de partes mecánicas

LA EMPRESA SERVICIOS. Reparación. Reparación de maquinaria eléctrica Sustitución de devanados de BT Mecanización de partes mecánicas CATÁLOGO SERVICIOS 2014 LA EMPRESA Mantenimiento Industrial RAE, S.L.U., es una empresa dedicada a la reparación y mantenimiento de maquinaria eléctrica. La empresa está ubicada en Castellón de la Plana,

Más detalles

NI 56.43.02. Unipolar cables with dry crosslinked. and polyolefine sheathing (Z1) for HV grids up to 30 kv. Julio de 2009 EDICION: 2ª

NI 56.43.02. Unipolar cables with dry crosslinked. and polyolefine sheathing (Z1) for HV grids up to 30 kv. Julio de 2009 EDICION: 2ª N O R M A NI 56.43.02 Julio de 2009 EDICION: 2ª I B E R D R O L A Cables unipolares con aislamiento seco de polietileno reticulado (XLPE) y cubierta de compuesto de poliolefina (Z1) para redes de AT hasta

Más detalles

ABB Switzerland Ltd, Micafil bushings Líder en producción de bornas en tecnología RIP y RIS

ABB Switzerland Ltd, Micafil bushings Líder en producción de bornas en tecnología RIP y RIS Lorenzo Martinel, PTMDV, Mayo 2013 ABB Switzerland Ltd, Micafil bushings Líder en producción de bornas en tecnología RIP y RIS June 19, 2013 Slide 1 Datos sobre ABB Switzerland Ltd, Localización Zurich

Más detalles

A2-210 MONITOREO CONTINUO DE EQUIPOS DE POTENCIA CON EMISIÓN ACÚSTICA. Physical Acoustics Corporation

A2-210 MONITOREO CONTINUO DE EQUIPOS DE POTENCIA CON EMISIÓN ACÚSTICA. Physical Acoustics Corporation II CONGRESO VENEZOLANO DE REDES Y ENERGÍA ELÉCTRICA Junio 29 Comité Nacional Venezolano A2-21 MONITOREO CONTINUO DE EQUIPOS DE POTENCIA CON EMISIÓN ACÚSTICA Arturo Nunez Eloy Gasperin Physical Acoustics

Más detalles

En este artículo se describe el desarrollo y la aplicación en campo de

En este artículo se describe el desarrollo y la aplicación en campo de Boletín IIE Evaluación de subestaciones eléctricas aisladas en gas Carlos G. Azcárraga R., Emmanuel Romero L. y Francisco Feregrino Pérez* En este artículo se describe el desarrollo y la aplicación en

Más detalles

K and M class flexible cables

K and M class flexible cables Anexo A Annex A Cables flexibles clase K y M K and M class flexible cables Cable flexible clase K Flexible cable class K Aplicaciones Este conductor de cobre se usa en la construcción de cables aislados

Más detalles

NORMA TÉCNICA COLOMBIANA 5717

NORMA TÉCNICA COLOMBIANA 5717 NORMA TÉCNICA NTC COLOMBIANA 5717 2009-10-21 CONDICIONES DE SERVICIO Y DEFINICIONES PARA FUSIBLES DE ALTA TENSIÓN, INTERRUPTORES AL AIRE MONOPOLARES DE DISTRIBUCIÓN ENCERRADOS, SECCIONADORES DE FUSIBLES

Más detalles

Normas IEC en el TC64 Reglas de instalación para baja tensión

Normas IEC en el TC64 Reglas de instalación para baja tensión 1 er Foro del Comité Electrotécnico Mexicano Normalización internacional - Productos confiables - Instalaciones eléctricas seguras Normas IEC en el TC64 Reglas de instalación para baja tensión 1 Concepción

Más detalles

Seminario de Electrónica Industrial

Seminario de Electrónica Industrial Elena Villanueva Méndez Parques eólicos y conexión a la red. Valparaíso, Junio de 2010 Parques eólicos Altas demandas dinámicas: Control de frecuencia y voltaje Control de potencia activa y reactiva Respuesta

Más detalles

CABLES PARA MOTORES CON VARIADORES DE FRECUENCIA VDF

CABLES PARA MOTORES CON VARIADORES DE FRECUENCIA VDF CABLES & TECNOLOGÍA BOLETÍN TÉCNICO - NOVIEMBRE 2012 CABLES PARA MOTORES CON VARIADORES DE FRECUENCIA VDF Variable Frequency Drive www.centelsa.com.co 1. ANTECEDENTE TÉCNICO Un variador de frecuencias,

Más detalles

NORMA TÉCNICA COLOMBIANA 4389

NORMA TÉCNICA COLOMBIANA 4389 NORMA TÉCNICA NTC COLOMBIANA 4389 2005-05-25 DESCARGADORES DE SOBRETENSIONES (PARARRAYOS) DE ÓXIDO METÁLICO SIN ESPACIADORES (GAPS) PARA SISTEMAS DE CORRIENTE ALTERNA E: SURGE ARRESTERS. METAL OXIDE SURGE

Más detalles

Arco eléctrico: estimación de la energía calorífica incidente sobre un trabajador

Arco eléctrico: estimación de la energía calorífica incidente sobre un trabajador Año: 011 904 Arco eléctrico: estimación de la energía calorífica incidente sobre un trabajador arc flash: estimation of thermal incident energy on worker arc électrique: estimation de l énergie calorifique

Más detalles

Terminaciones de MT Serie QT-III 5/35kV IEEE

Terminaciones de MT Serie QT-III 5/35kV IEEE Ficha Técnica Descripción Las Terminaciones Contraíbles en Frío QT-III, contienen en una sola pieza el control de esfuerzos eléctricos, el aislamiento y los sellos contra la humedad. Aprobadas bajo el

Más detalles

DISEÑO Y VALIDACIÓN A FATIGA DE UN VÁSTAGO DE REVISIÓN DE PRÓTESIS DE CADERA EMPLEANDO EL MÉTODO DE LOS ELEMENTOS FINITOS

DISEÑO Y VALIDACIÓN A FATIGA DE UN VÁSTAGO DE REVISIÓN DE PRÓTESIS DE CADERA EMPLEANDO EL MÉTODO DE LOS ELEMENTOS FINITOS DISEÑO Y VALIDACIÓN A FATIGA DE UN VÁSTAGO DE REVISIÓN DE PRÓTESIS DE CADERA EMPLEANDO EL MÉTODO DE LOS ELEMENTOS FINITOS F. J. Vigil 1, M. A. Guerrero 1, J. Jorge 1, S. Rivera 1, A. Iglesias 2 1 Fundación

Más detalles

REGLAMENTO TECNICO CONDUCTORES Y CABLES ELECTRICOS

REGLAMENTO TECNICO CONDUCTORES Y CABLES ELECTRICOS REGLAMENTO TECNICO CONDUCTORES Y CABLES ELECTRICOS Artículo º Objeto.- El presente Reglamento Técnico tiene por finalidad establecer las características técnicas, así como, el rotulado y etiquetado, que

Más detalles

FASETRON TRANSFORMADORES ELECTRICOS CATALOGO DE PRODUCTOS

FASETRON TRANSFORMADORES ELECTRICOS CATALOGO DE PRODUCTOS FASETRON TRANSFORMADORES ELECTRICOS TRANSFORMADORES ELECTRICOS MARCA FASETRON FASETRON S.A. Actúa desde 1998 produciendo Transformadores de distribución y energía eléctrica para el mercado nacional. Utilizando

Más detalles

A continuación se describe con mayor detalle cada una de las unidades: UNIDAD 2: Calidad en el desarrollo, adquisición, operación y mantenimiento del

A continuación se describe con mayor detalle cada una de las unidades: UNIDAD 2: Calidad en el desarrollo, adquisición, operación y mantenimiento del 1. OBJETIVOS: Incorporar los conceptos de indicador, métrica, medida, escala de medición, y proceso de medición. Entender la importancia de los indicadores de desempeño de procesos, su medición y seguimiento.

Más detalles

GESTIÓN DE CALIDAD EN LOS LABORATORIOS DE PRUEBAS VETERINARIAS

GESTIÓN DE CALIDAD EN LOS LABORATORIOS DE PRUEBAS VETERINARIAS CAPÍTULO I.1.2. GESTIÓN DE CALIDAD EN LOS LABORATORIOS DE PRUEBAS VETERINARIAS RESUMEN Es esencial para el diagnóstico, la vigilancia y la comercialización que los resultados del laboratorio sean válidos.

Más detalles

FUSIBLES CILÍNDRICOS MT PARA APLICACIONES DE ALUMBRADO MV CYLINDRICAL FUSE-LINKS FOR LIGHTING PURPOSES

FUSIBLES CILÍNDRICOS MT PARA APLICACIONES DE ALUMBRADO MV CYLINDRICAL FUSE-LINKS FOR LIGHTING PURPOSES FUSIBLES CILÍNDRICOS MT PARA APLICACIONES DE ALUMBRADO MV CYLINDRICAL FUSE-LINKS FOR LIGHTING PURPOSES DF, S.A C/. Silici, 67-69 08940 CORNELLA DEL LLOBREGAT BARCELONA (SPAIN) www.df-sa.es Telf.: +34-93

Más detalles

EMPALMES EN CABLES SUTERRANEOS REFLECTOMETRIA CONVENCIONAL Y CAMBIOS DE IMPEDANCIAS

EMPALMES EN CABLES SUTERRANEOS REFLECTOMETRIA CONVENCIONAL Y CAMBIOS DE IMPEDANCIAS EMPALMES EN CABLES SUTERRANEOS REFLECTOMETRIA CONVENCIONAL Y CAMBIOS DE IMPEDANCIAS INTRODUCCION: Mas allá de la calidad de confección de un empalme que formará parte de un cable de energia, la gráfica

Más detalles

DISEÑO DE UN SENSOR DE TRANSFERENCIA DE CAMPO ELECTRICO. Ing. Pablo A. Perri

DISEÑO DE UN SENSOR DE TRANSFERENCIA DE CAMPO ELECTRICO. Ing. Pablo A. Perri DISEÑO DE UN SENSOR DE TRANSFERENCIA DE CAMPO ELECTRICO Ing. Pablo A. Perri Centro de Investigación y Desarrollo en Telecomunicaciones, Electrónica e Informática - CITEI Instituto Nacional de Tecnología

Más detalles

KEOR HP. SAI TRIFÁSICO de 100 a 800 kva ESPECIALISTA MUNDIAL EN INFRAESTRUCTURAS ELÉCTRICAS Y DIGITALES

KEOR HP. SAI TRIFÁSICO de 100 a 800 kva ESPECIALISTA MUNDIAL EN INFRAESTRUCTURAS ELÉCTRICAS Y DIGITALES KEOR HP SAI TRIFÁSICO de 100 a 800 kva ESPECIALISTA MUNDIAL EN INFRAESTRUCTURAS ELÉCTRICAS Y DIGITALES SAI Legrand RENDIMIENTO SUPERIOR CONTINUIDAD DEL SERVICIO Y EFICIENCIA ENERGÉTICA Legrand, líder mundial

Más detalles

Interamerican Accreditation Cooperation

Interamerican Accreditation Cooperation Interamerican Accreditation Cooperation DOCUMENTO INFORMATIVO DE IAAC ACREDITACIÓN Y CERTIFICACIÓN DE LABORATORIOS EL PAPEL DE ISO/IEC 17025 E ISO 9001 1 Antecedentes Como resultado de algunos malentendidos

Más detalles

8 TABLA DE INTENSIDADES MÁXIMAS ADMI SIBLES EN SERVICIO PERMANENTE

8 TABLA DE INTENSIDADES MÁXIMAS ADMI SIBLES EN SERVICIO PERMANENTE 8 TABLA DE INTENSIDADES MÁXIMAS ADMI SIBLES EN SERVICIO PERMANENTE 8. CONDICIONES DE INSTALACIÓN En las tablas 6 a 9 se dan las intensidades máximas admisibles en régimen permanente para los cables con

Más detalles

CURRÍCULUM VITAE: MARCOS MORENO BARRAZA Datos Generales Lugar de nacimiento: DELICIAS, CHIH., MÉXICO, Fecha de Nacimiento: 20/01/1941

CURRÍCULUM VITAE: MARCOS MORENO BARRAZA Datos Generales Lugar de nacimiento: DELICIAS, CHIH., MÉXICO, Fecha de Nacimiento: 20/01/1941 CURRÍCULUM VITAE: MARCOS MORENO BARRAZA Datos Generales Lugar de nacimiento: DELICIAS, CHIH., MÉXICO, Fecha de Nacimiento: 20/01/1941 1. FORMACIÓN ACADÉMICA PROFESIONAL (1) Licenciatura en Ingeniería Eléctrica.

Más detalles

ESPECIFICACIÒN TÈCNICA E.T. 99.03/1 CUBIERTA PROTECTORA PARA CONDUCTOR DESNUDO DE MEDIA TENSION FECHA DE APROBACIÓN: 09/04/02

ESPECIFICACIÒN TÈCNICA E.T. 99.03/1 CUBIERTA PROTECTORA PARA CONDUCTOR DESNUDO DE MEDIA TENSION FECHA DE APROBACIÓN: 09/04/02 ESPECIFICACIÒN TÈCNICA E.T. 99.03/1 CUBIERTA PROTECTORA PARA CONDUCTOR DESNUDO DE MEDIA TENSION FECHA DE APROBACIÓN: 09/04/02 E.T. 99.03/1-08/06/01 INDICE 1. - OBJETO...1 2. - CAMPO DE APLICACIÓN...1 3.

Más detalles

1. QUÉ SON LOS ARMÓNICOS?

1. QUÉ SON LOS ARMÓNICOS? POWER ELECTRONICS ARMÓNICOS EN SECTORES INDUSTRIALES 1. QUÉ SON LOS ARMÓNICOS? Se puede demostrar que cualquier forma de onda periódica (repetitiva) puede ser representada como una serie de ondas senoidales

Más detalles

ENSA Código: NO.MA.08.09

ENSA Código: NO.MA.08.09 ENSA Código: NO.MA.08.09 Departamento de Normas Especificación Técnica Cable para Medio Voltaje de Cobre con Neutro Concéntrico Fecha de Creación: 10-oct-11 Fecha de Última Actualización: 18-abr-13 Versión:

Más detalles

Centros de Distribución de Potencia. Ing. Luis Fernando Brizuela Castillo

Centros de Distribución de Potencia. Ing. Luis Fernando Brizuela Castillo Centros de Distribución de Potencia Ing. Luis Fernando Brizuela Castillo Ingeniería para el ahorro y eficiencia en la distribución de la energía eléctrica 1.- Normatividad aplicable para el diseño y la

Más detalles

Metodología para la renovación eficiente de redes basada en riesgo de discontinuidad del servicio.

Metodología para la renovación eficiente de redes basada en riesgo de discontinuidad del servicio. IV Jornadas de Ingeniería del Agua La precipitación y los procesos erosivos Córdoba, 21 y 22 de Octubre 2015 Metodología para la renovación eficiente de redes basada en riesgo de discontinuidad del servicio.

Más detalles

Mantenimiento predictivo de transformadores de potencia Sistema trifásico completo Relación de Transformación: Tensión de Reabsorción:

Mantenimiento predictivo de transformadores de potencia Sistema trifásico completo Relación de Transformación: Tensión de Reabsorción: SISTEMA ETP Mantenimiento predictivo de transformadores de potencia El mantenimiento predictivo es la solución más eficiente para asegurar el correcto funcionamiento de elementos críticos como los transformadores

Más detalles

CURSO DE METROLOGÍA INDUSTRIAL

CURSO DE METROLOGÍA INDUSTRIAL 15/3/21 CURSO DE METROLOGÍA INDUSTRIAL TEMARIO REDUCIDO Metrología básica Medición de temperatura Medición de presión Medición de caudal Medición de variables químicas Controladores P+I+D 1 15/3/21 Para

Más detalles

Básculas y Balanzas Barcelona FICHA DE PRODUCTO. Ohaus MB. Balanza analizador de humedad

Básculas y Balanzas Barcelona FICHA DE PRODUCTO. Ohaus MB. Balanza analizador de humedad Básculas y Balanzas Barcelona FICHA DE PRODUCTO Ohaus MB Balanza analizador de humedad Web con precios y versiones: basculas-balanzas.com > Ohaus MB Série MB Analizadores de Humedad MB35 MB45 Desde equipos

Más detalles

VISTO: El Expediente ENRE N 4431/97 y las Resoluciones SE N 15/92, N 137/92 y N 77/98,y

VISTO: El Expediente ENRE N 4431/97 y las Resoluciones SE N 15/92, N 137/92 y N 77/98,y Resolución ENRE 1724/1998. Boletín Oficial n 29.038, lunes 7 de diciembre de 1998, pp. 25-26. Citas Legales : Res. SE 15/92; Res. SE 137/92; Res. SE 77/98; Res. ENRE 32/94 BUENOS AIRES, 26 DE NOVIEMBRE

Más detalles

La implementación del control de equipo de monitoreo y medición en los sistemas de calidad industriales para ase-

La implementación del control de equipo de monitoreo y medición en los sistemas de calidad industriales para ase- Año 04 # 09 2004-septiembre Herramientas de la Metrología en Sistemas de Calidad MetAs & Metrólogos Asociados La Guía MetAs La implementación del control de equipo de monitoreo y medición en los sistemas

Más detalles

CUADERNO TÉCNICO: CALIBRACIÓN DE EQUIPOS DE MEDIDA INDUSTRIALES SEGÚN ISO 9000

CUADERNO TÉCNICO: CALIBRACIÓN DE EQUIPOS DE MEDIDA INDUSTRIALES SEGÚN ISO 9000 CUADERNO TÉCNICO: CALIBRACIÓN DE EQUIPOS DE MEDIDA INDUSTRIALES SEGÚN ISO 9000 Adolfo Hilario - ahilario@isa.upv.es Pablo Carbonell pjcarbon@isa.upv.es Departamento de Ingeniería de Sistemas y Automática

Más detalles

4 CONCLUSIONES Y RECOMENDACIONES

4 CONCLUSIONES Y RECOMENDACIONES - 142-4 CONCLUSIONES Y RECOMENDACIONES 4.1 CONCLUSIONES - El continuo crecimiento de los niveles de cargabilidad de los elementos del SEP, el uso de nuevas tecnologías y controles, así como las interconexiones

Más detalles

PROYECTO TIPO PARA CENTRO DE TRANSFORMACIÓN INTEGRADO Ó COMPACTO EN ENVOLVENTE PREFABRICADA SUBTERRÁNEA

PROYECTO TIPO PARA CENTRO DE TRANSFORMACIÓN INTEGRADO Ó COMPACTO EN ENVOLVENTE PREFABRICADA SUBTERRÁNEA MT 2.11.09 Edición 01 Fecha: Abril, 2004 MANUAL TÉCNICO DE DISTRIBUCIÓN PROYECTO TIPO PARA CENTRO DE TRANSFORMACIÓN INTEGRADO Ó COMPACTO EN ENVOLVENTE PREFABRICADA SUBTERRÁNEA MT 2.11.09 Edición 01 Fecha:

Más detalles

Área de Distribución y Comercialización Identificación del Trabajo: CO-90 Maceió, Brasil, Agosto de 2005

Área de Distribución y Comercialización Identificación del Trabajo: CO-90 Maceió, Brasil, Agosto de 2005 COMISIÓN DE INTEGRACIÓN ENERGÉTICA REGIONAL COMITÉ NACIONAL COLOMBIANO V CIERTEC - SEMINARIO INTERNACIONAL SOBRE GESTIÓN DE PÉRDIDAS, EFICIENCIA ENERGÉTICA Y PROTECCIÓN DE LOS INGRESOS EN EL SECTOR ELÉCTRICO

Más detalles

RepublicofEcuador EDICTOFGOVERNMENT±

RepublicofEcuador EDICTOFGOVERNMENT± RepublicofEcuador EDICTOFGOVERNMENT± Inordertopromotepubliceducationandpublicsafety,equaljusticeforal, abeterinformedcitizenry,theruleoflaw,worldtradeandworldpeace, thislegaldocumentisherebymadeavailableonanoncommercialbasis,asit

Más detalles

Interruptores de alta tensión. para aplicaciones de hasta 800 kv

Interruptores de alta tensión. para aplicaciones de hasta 800 kv Interruptores de alta tensión para aplicaciones de hasta 800 kv La tecnología del mañana se basa en las experiencias de hoy ABB cuenta con toda la experiencia necesaria para desarrollar con éxito la tecnología

Más detalles

NORMA TECNICA COLOMBIANA

NORMA TECNICA COLOMBIANA NORMA TECNICA COLOMBIANA NTC-18001 Sistema de Gestión en Seguridad y Salud Ocupacional NORMA TECNICA COLOMBIANA NTC-18001 Sistema de Gestión en Seguridad y Salud Ocupacional CORRESPONDENCIA: Esta norma

Más detalles

NORMA DE DISTRIBUCIÓN NO-DIS-MA-5001 TRANSFORMADORES DE CORRIENTE DE MEDIDA Y PROTECCIÓN FECHA DE APROBACIÓN: 2015/07/01

NORMA DE DISTRIBUCIÓN NO-DIS-MA-5001 TRANSFORMADORES DE CORRIENTE DE MEDIDA Y PROTECCIÓN FECHA DE APROBACIÓN: 2015/07/01 NORMA DE DISTRIBUCIÓN NO-DIS-MA-5001 TRANSFORMADORES DE CORRIENTE DE MEDIDA Y FECHA DE APROBACIÓN: 2015/07/01 ÍNDICE 0.- REVISIONES... 2 1.- OBJETO Y CAMPO DE APLICACIÓN... 3 2.- DEFINICIONES/SÍMBOLOS/ABREVIATURAS...

Más detalles

Productos. Reactores o Creadores de Neutro Artificial en 36 kv. BRC0111V4

Productos. Reactores o Creadores de Neutro Artificial en 36 kv. BRC0111V4 75 / 75 / 25 MVA 230 / 138 / 13.8 kv Productos Transformadores de Potencia hasta 300 MVA en tensiones hasta 230 kv. Elevador Reductor Transformadores de Horno Transformadores de Tracción Especiales Subestación

Más detalles

ebiflabkq mirp fåëééååáμå=ó=ã~åíéåáãáéåíç=ó= ÅçãéêçÄ~Åáμå=í ÅåáÅ~=ÇÉ=ëÉÖìêáÇ~Ç PLUS HELIODENT PLUS PLUS 7mA DC 7mA DC

ebiflabkq mirp fåëééååáμå=ó=ã~åíéåáãáéåíç=ó= ÅçãéêçÄ~Åáμå=í ÅåáÅ~=ÇÉ=ëÉÖìêáÇ~Ç PLUS HELIODENT PLUS PLUS 7mA DC 7mA DC 7mA DC 7mA DC ebiflabkq mirp fåëééååáμå=ó=ã~åíéåáãáéåíç=ó= ÅçãéêçÄ~Åáμå=í ÅåáÅ~=ÇÉ=ëÉÖìêáÇ~Ç 008S. PLUS HELIODENT PLUS 70kV 60kV 008S. 70kV 60kV PLUS HELIODENT Sirona Dental Systems GmbH Estimado cliente:

Más detalles

PROYECTO DISEÑO Y CONSTRUCCIÓN DE UN MONITOR DE SIGNOS VITALES BASADO EN UN COMPUTADOR PORTÁTIL PRODUCTO INTERMEDIO P14 MÓDULO FUENTE DE ALMIENTACIÓN

PROYECTO DISEÑO Y CONSTRUCCIÓN DE UN MONITOR DE SIGNOS VITALES BASADO EN UN COMPUTADOR PORTÁTIL PRODUCTO INTERMEDIO P14 MÓDULO FUENTE DE ALMIENTACIÓN PROYECTO DISEÑO Y CONSTRUCCIÓN DE UN MONITOR DE SIGNOS VITALES BASADO EN UN COMPUTADOR PORTÁTIL PRODUCTO INTERMEDIO P14 MÓDULO FUENTE DE ALMIENTACIÓN ACTIVIDADES: A14 1: Pruebas de la Fuente de Alimentación

Más detalles

REGLAMENTO : SEGURIDAD DE INSTALACIONES DESTINADAS A LA PRODUCCIÓN, TRANSFORMACIÓN, TRANSPORTE Y DISTRIBUCIÓN DE ENERGÍA ELÉCTRICA.

REGLAMENTO : SEGURIDAD DE INSTALACIONES DESTINADAS A LA PRODUCCIÓN, TRANSFORMACIÓN, TRANSPORTE Y DISTRIBUCIÓN DE ENERGÍA ELÉCTRICA. DIVISIÓN DE INGENIERÍA DE ELECTRICIDAD PLIEGO TÉCNICO NORMATIVO : RPTD N 4. MATERIA : CONDUCTORES. REGLAMENTO : SEGURIDAD DE INSTALACIONES DESTINADAS A LA PRODUCCIÓN, TRANSFORMACIÓN, TRANSPORTE Y DISTRIBUCIÓN

Más detalles

Un par de puntas de prueba que comunican el instrumento con el circuito bajo prueba.

Un par de puntas de prueba que comunican el instrumento con el circuito bajo prueba. INSTRUMENTACIÓN ELÉCTRICA Medición de tensión con diferentes instrumentos de medida MULTÍMETROS ANALOGOS De todas las herramientas y equipos que un electricista pueda poseer en su banco o en su maletín

Más detalles

Medición en campo de la potencia máxima entregada por paneles fotovoltaicos bajo condiciones estándar de medida

Medición en campo de la potencia máxima entregada por paneles fotovoltaicos bajo condiciones estándar de medida Medición en campo de la potencia máxima entregada por paneles fotovoltaicos bajo condiciones estándar de medida M.A. Muñoz 1, P. Cabrera 1, G. Moreda 1, F. Chenlo 2 1 Dep. Ingeniería Rural. Electrotecnia,

Más detalles

Servicios para Transformadores

Servicios para Transformadores Servicios para Transformadores INTELLIGENT TRANSFORMER MANAGEMENT Conocimiento, Experiencia, Pericia. Sus clientes dependen de Energía Segura, Confiable e Ininterrumpida. La necesidad de aplicar principios

Más detalles

Trabajo eficaz con la mayor Seguridad para sus trabajadores e instalaciones

Trabajo eficaz con la mayor Seguridad para sus trabajadores e instalaciones Trabajo eficaz con la mayor Seguridad para sus trabajadores e instalaciones Herramientas de gran seguridad para el mantenimiento eficaz de redes eléctricas Saber qué hacer y cómo conseguirlo Lo primero

Más detalles