1. Fecha : lunes, 22 de febrero de 2016 2. Hora de Inicio : 05:00 h 3. Evento : 4. Propietario : SPCC 5. Causa del Evento : Desconexión de la línea L-5034 (Poroma Ocoña), L-5036 (Ocoña - San José) y L-5037 (San José- Montalvo) de 500 kv. 6. Condiciones operativas previas N GENERACIÓN LOCAL SUBESTACIÓN ACTIVA (MW) REACTIVA (MVAR) 1 CT Ilo1 Ilo1 35.0 7.0 2 CT Ilo2 Ilo2 (SE Moquegua 220kV) -2.6 34.0 3 Pan. Solar Panamericana Solar 0.0 1.1 N CÓDIGO DESDE LINEA ACTIVA (MW) REACTIVA (MVAR) 1 L-1025 Moquegua Toquepala 42.8 14.7 2 L-1384 Moquegua Millsite 43.8 15.0 3 L-1381 Moquegua Botiflaca 69.2 7.0 4 L-1382 Moquegua Botiflaca 0.0 0.0 5 L-1389 Millsite Totoral 20.2 4.4 6 L-1386/2 Push Back Millsite -12.6 2.2 7 L-1386/1 Botiflaca Push Back -3.7 7.6 8 L-1388 Toquepala Millsite 41.5 12.0 9 L-1385/2 Ilo 3 Quebrada Honda -9.6-2.1 10 L-1385/1 Q. Honda Millsite -11.4-3.8 11 L-1392 Electrosur Ilo 3-9.3-10.5 12 L-1391 Ilo 1 Electrosur -5.5-10.6 13 L-1387 Ilo 1 Refinería -10.7-3.9 14 L-1383 Ilo 1 Moquegua -49.5 5.9 15 L-1390 Ilo 3 Panamericana Solar 0.0-1.1 Cargas por Subestación previas al Evento: SUBESTACIÓN MW Botiflaca 75.6 Push Back 13.6 Millsite 42.4 Quebrada Honda 3.8 Lixiviación 24.1 Fundición 35.9 Refinería 10.6 TOTAL 206.0 Centro de Control de Energía Pág. 1 de 7
LINEAS DE TRANSMISION CÓDIGO ESTADO Moquegua - Toquepala L-1025 E.S Moquegua - Mill Site L-1384 E.S Moquegua - Botiflaca L-1381 E.S Moquegua - Botiflaca L-1382 F.S Mill Site Totoral L-1389 E.S Push Back - Mill Site L-1386/2 E.S Botiflaca - Push Back L-1386/1 E.S Toquepala - Mill Site L-1388 E.S Ilo3 Quebrada Honda L-1385/2 E.S Q. Honda - Mill Site L-1385/1 E.S ELECTROSUR - Ilo3 L-1392 E.S Ilo1 ELECTROSUR L-1391 E.S Ilo1 - Derv. Refinería L-1387 E.S Ilo1 Moquegua L-1383 E.S Ilo3 - Pan. Solar L-1390 E.S Nota: 7. Descripción del Evento E.S: Línea en servicio. F.S: Línea fuera de servicio. A las 05:00 h. se produjo la desconexión de las líneas L-5034 (Poroma Ocoña), L-5036 (Ocoña San José) y L-5037 (San José - Montalvo) de 500 kv por falla monofásica a tierra en la fase S de la línea L-5034 (Poroma Ocoña). En consecuencia, se produjo la reducción de carga en SPCC de 64.1 MW (Concentradora Cuajone: 33.1 MW, Concentradora Toquepala: 6.6 MW, Lixiviación: 10.4 MW, Quebrada Honda: 0.8 MW, Mina Toquepala: 6.8 MW, Fundición: 6.4 MW). 8. Secuencia de Eventos HORA 05:00 DESCRIPCIÓN Desconexión de la líneas L-5034 (Poroma Ocoña), L-5036 (Ocoña San José) y L- 5037 (San José - Montalvo) 05:00 SPCC redujo su carga en 64.1 MW. 05:02 Desconexión de la línea L-5037 por sobre tensión, según informado por CC-ATS. 05:10 Se coordinó con CC-ENS recuperar el suministro interrumpido 05:15 Se energizó la línea L-5037 desde la SE Montalvo. 06:23 Se energizó la línea L-5034 (Poroma Ocoña) desde Poroma. 06:26 Se energizó la línea L-5036 (Ocoña San José) desde la SE Ocoña. 06:32 Se conectó la línea L-5036 en la SE San José, con lo cual se cierra el anillo Centro-Sur Centro de Control de Energía Pág. 2 de 7
9. Registro de demandas SPCC INFORME FINAL DE EVENTO 40 35 30 25 20 15 10 5 35.14 MW ILO 0 04:30:00.000 a.m. 04:34:00.000 a.m. 04:38:00.000 a.m. 04:42:00.000 a.m. 04:46:00.000 a.m. 04:50:00.000 a.m. 04:54:00.000 a.m. 04:58:00.000 a.m. 05:02:00.000 a.m. 05:06:00.000 a.m. 05:10:00.000 a.m. 05:14:00.000 a.m. 05:18:00.000 a.m. 05:22:00.000 a.m. 05:26:00.000 a.m. 05:30:00.000 a.m. 05:34:00.000 a.m. 05:38:00.000 a.m. 05:42:00.000 a.m. 05:46:00.000 a.m. 05:50:00.000 a.m. 05:54:00.000 a.m. 05:58:00.000 a.m. 06:02:00.000 a.m. 06:06:00.000 a.m. 06:10:00.000 a.m. 06:14:00.000 a.m. 06:18:00.000 a.m. ILO_Refi ILO_Fundi ILO_Cam_Coq ILO_Electrosur 06:22:00.000 a.m. 06:26:00.000 a.m. 06:30:00.000 a.m. Perfil de carga de Ilo (MW) (Fuente: Sistema ION) CUAJONE 45 40 38.9 MW 05:01 h 35 30 25 27.23 MW 20 15 10 5 0 04:30:00.000 a.m. 04:35:00.000 a.m. 04:40:00.000 a.m. 04:45:00.000 a.m. 04:50:00.000 a.m. 04:55:00.000 a.m. 05:00:00.000 a.m. 05:05:00.000 a.m. 05:10:00.000 a.m. 05:15:00.000 a.m. 05:20:00.000 a.m. 05:25:00.000 a.m. 05:30:00.000 a.m. 05:35:00.000 a.m. 05:40:00.000 a.m. 05:45:00.000 a.m. 05:50:00.000 a.m. 05:55:00.000 a.m. 06:00:00.000 a.m. 06:05:00.000 a.m. 06:10:00.000 a.m. 06:15:00.000 a.m. 06:20:00.000 a.m. 06:25:00.000 a.m. 06:30:00.000 a.m. CUA_Mina CUA_Ch+Aux CUA_Moli Perfil de carga de Cuajone (MW) (Fuente: Sistema ION) Centro de Control de Energía Pág. 3 de 7
45 40 35 30 25 20 15 40.6 MW 23 MW 13.6 MW TOQUEPALA 10 5 3.8 MW 0 04:30:00.000 a.m. 04:35:00.000 a.m. 04:40:00.000 a.m. 04:45:00.000 a.m. 04:50:00.000 a.m. 04:55:00.000 a.m. 05:00:00.000 a.m. 05:05:00.000 a.m. 05:10:00.000 a.m. 05:15:00.000 a.m. 05:20:00.000 a.m. 05:25:00.000 a.m. 05:30:00.000 a.m. 05:35:00.000 a.m. 05:40:00.000 a.m. 05:45:00.000 a.m. 05:50:00.000 a.m. 05:55:00.000 a.m. 06:00:00.000 a.m. 06:05:00.000 a.m. 06:10:00.000 a.m. 06:15:00.000 a.m. 06:20:00.000 a.m. 06:25:00.000 a.m. 06:30:00.000 a.m. TOQ_Mina TOQ_Conc TOQ_Lixi TOQ_QueH TOQ_Camp TOQ_DLix 10. Registros de tensión Perfil de carga de Toquepala (MW) (Fuente: Sistema ION) Registro de tensión SE Moquegua Barra 1-138 kv (Fuente: Registrador de fallas SE Moquegua) Centro de Control de Energía Pág. 4 de 7
Registro de tensión SE Fundición VCB 661-13.8 kv (Fuente: Registrador de fallas RF 01-1 SE Fundición) Registro de tensión SE Millsite HCB 753-138 kv (Fuente: Registrador de fallas RF08-1 SE Millsite) Centro de Control de Energía Pág. 5 de 7
Registro de tensión SE Botiflaca HCB 856-138 kv (Fuente: Registrador de fallas RF09-5 SE Botiflaca) 11. Consecuencias Carga interrumpida fue la siguiente: UNIDAD OPERATIVA SUBESTACIÓN Y/O AREA OPERATIVA CARGA HORA INICIO A PERDIDA SALIDA RECUPERAR [MW] [hh:mm] [hh:mm] Chancadoras 11.6 05:00 05:45 CUAJONE Molinos 21.5 05:00 05:23 Mina - - - Campamentos - - - Concentradora 6.6 05:00 05:10 TOQUEPALA Lixiviación + Dep Lix. 10.4 05:00 05:17 Quebrada Honda 0.8 05:00 05:32 Mina 6.8 05:00 05:10 Fundición 6.4 05:00 05:48 ILO Refinería - - - Campamento Coquina - - - TOTAL 64.1 Centro de Control de Energía Pág. 6 de 7
12. Observaciones - Debido al evento, SPCC interrumpió 64.1 MW. 13. Anexos - Se adjunta archivos COMTRADE. ELABORADO REVISADO FECHA Percy Sedano Wille Castellanos Edwin Gómez Melanni Iparraguirre Luis Toledo 22/02/2016 Centro de Control de Energía Pág. 7 de 7