Member AQUAFOG Components (High Pressure)
Micro-nozzle: AQUAFOG Nozzles Type 1: k = 0.11 l/(min bar 0.5 ) Type 2: k = 0.27 l/(min bar 0.5 ) Type 3: k = 0.46 l/(min bar 0.5 ) Type 4: k = 0.76 l/(min bar 0.5 ) Type 6: k = 0.12 l/(min bar 0.5 ) Type 7: k = 0.20 l/(min bar 0.5 ) [ l / min] = k P Q
AQUAFOG Nozzles Open Closed Heat/Pneumatic T type SMD 50 μm
AQUAFOG Nozzles (Open)
AQUAFOG Nozzles (Closed) RTI=36 [m s] 1/2
AQUAFOG Nozzles (Heat/Pneumatic) RTI=36 [m s]1/2
AQUAFOG Nozzles (T type)
Selector Valve 24 VDC 18 W Pmax: 140 bar VDH30 30 l/min VDH60 60 l/min VDH120 120 l/min
Bank of Cylinders (Deluge Systems) Kits activated by explosor: 2 Cylinders Water - 1 Nitrogen (200 bar) (26, 50, 67 5 y 80 liters) 3 Cylinders Water -1 Nitrogen (200 bar) (67 5 y 80 liters) 4 Cylinders Water 2 Nitrogen (200 bar) (67 5 y 80 liters) 5 Cylinders Water 2 Nitrogen (200 bar) (80 liters) 6 Cylinders Water - 2 Nitrogen (200 bar) (80 liters) 7 Cylinders Water 3 Nitrogen (200 bar) (80 liters)... 12 Cylinders Water - 4 Nitrogen (200 bar) (80liters) Modular @ 80 bar (kitchen protection)
Bank of Cylinders (Deluge Systems)
Bank of Cylinders (Deluge Systems)
Bank of Cylinders (Wet Systems) Kits activated by neumatic valve: - 2 Cylinders Water - 1 Nitrogen (200 bar) (26, 50, 67 5 y 80 liters) - 3 Cylinders Water -1 Nitrogen (200 bar) (67 5 y 80 liters) - 4 Cylinders Water 2 Nitrogen (200 bar) (67 5 y 80 liters) - 5 Cylinders Water 2 Nitrogen (200 bar) (80 liters) - 6 Cylinders Water - 2 Nitrogen (200 bar) (80 liters) - 7 Cylinders Water 3 Nitrogen (200 bar) (80 liters)... - 12 Cylinders Water - 4 Nitrogen (200 bar) (80liters)
1 2 1 2 Fire Extinguishing Systems Bank of Cylinders (Wet Systems) Pneumatic valve keeps pipe at a constant pressure of 15 bar. In case of nozzle activation all nitrogen cylinders will discharge. In case of small leakage in the pipe network nitrogen in the master cylinder will compensate the leakage.
Flow rate (lpm) 44 86 112 2 x 86 2 x 112 Power (kw) 15 30 37 60 74 Pressure Relief Valve Flow rate (lpm) 60 120 120 240 240 Pump systems are suitable for total flooding systems and wet pipe systems (includes Jockey pump). Systems are delivered with PPH vertical tank and control panel.
Pump system components 3 2 11 4 10 9 1 13 8 2 6 7 5 12 14
A. Water Supply Water supply is based on: Different tank sizes in accordance to flow rate and discharge time. Tanks are completed with high and low level detector. Connection to water main through filter and float valve.
A. Water Supply Tank PPH from 300 up to 3.000 liters Level detector: High level: confirms tank is full Low level: stops pump Filter Grid size: 10 μm Maximum pressure: 10 bar Valves Float valve Ball valves for maintenance purposes
A. Water Supply TAPA ENCAJE RESPIRADERO 1" ACODADO CON REJILLA FILTRO DE AGUA DE RED CONEXIÓN A BORNAS 33/34 VALVULA DE FLOTADOR DEPOSITO VISTA A DEPOSITO VISTA B SALIDA ASPIRACION CONEXI N A BORNAS 31/32 2 CABLES AISLADOS 750 V DE 1 mm EN INTERIOR TUBO COARRUGADO PG7
B. Pump High pressure positive displacement pump with a triphasic engine, aspiration and impulsion stainless steel manifold. System is completed with pressure gauges, pressure switches, ball valves, hoses. System is mounted on a steel frame.
B. Pump Pump Positive displacement pump ( 9 pistons) Water self-lubricated Maximum pressure: 160 bar Speed: 1.500 rpm Jockey: 1,1 lpm, 750 rpm Engine 220/380 V 50 Hz Star-Triangle start up IP55
B. Pump Pressure Relief Valve Actuation pressure: 120 160 bar Pressure transducter Pressure: 0-250 bar
B. Pump 7 10 6 5 4 2 9 3 1 Vista longitudinal bombeo 8 Detalle vista frontal colectores # Descripción # Descripción 1 Latiguillo trenzado aspiración 6 Transductor de presión 0-250 bar 2 Grupo bomba-motor 7 Válvula sobrepresión 3 Colector aspiración 8 Válvula antirretorno 4 Colector impulsión 9 Latiguillo AP impulsión 5 Manómetro glicerina 0-315 bar 10 Válvula de bola PN-300
B. Pump Example of multiple pump systems
Control panel: C. Control Panel Tactile terminal: Shows different system and element states. Shows alarms and keeps historic of alarms. Leds (Shows main states: System OK, Fault, Off) Acoustic signal (activates in case of alarm or pump activation). Emergency STOP Activation Button
C. Control Panel CE mark 220/380 AC Triphasic Output signals: System OK Electrical failure (24 VAC/phases) Start up failure Pump running System ON Tank level
0 Fire Extinguishing Systems Deluge System RIESGO Nº1 3 Cabezal abierto 2 Detector 1 Tubería acero inox. AISI 316L Posi ción Descri pción 1 EQUIPO DE BOMBEO PARA AGUA NEBULIZADA. INUNDACIÓN TOTAL ENTRADA ALIMENTACIÓN RED MUNICIPAL RIESGO Nº2 A SISTEMA 24 V 24 V SEÑAL DE ACTUACIÓN SISTEMA ON INVERSIÓN FASES PANEL AVERÍA CONTROL BOMBA EN FUNCIONAMIENTO SEÑAL CONFIRMACIÓN EXTINCIÓN 220/380 3N 50Hz NIVEL DEPÓSITO BAJO CENTRALITA SEÑAL DE DETECTORES 2 3 SEÑAL DETECTORES RIESGO Nº1 Y Nº2
0 Fire Extinguishing Systems Deluge System with Selector Valves 5 Válvula by-pass 4 Válvula direccional 3 Cabezal abierto 2 Detector 1 Tubería acero inox. AISI 316L Posi ción Descri pción 1 4 5 RIESGO Nº1 EQUIPO DE BOMBEO PARA AGUA NEBULIZADA. INUNDACIÓN TOTAL CON VÁLVULAS DIRECCIONALES ENTRADA ALIMENTACIÓN RED MUNICIPAL RIESGO Nº2 A SISTEMA 24 V PANEL CONTROL 3N 220/380 50Hz 24 V SEÑAL DE ACTUACIÓN SISTEMA ON INVERSIÓN FASES AVERÍA BOMBA EN FUNCIONAMIENTO SEÑAL CONFIRMACIÓN EXTINCIÓN NIVEL DEPÓSITO BAJO CENTRALITA SEÑAL DE DETECTORES 2 3 SEÑAL DETECTORES RIESGO Nº2 SEÑAL DETECTORES RIESGO Nº1
0 Fire Extinguishing Systems Wet System RIESGO Nº1 2 Cabezal cerrado 1 Tubería acero inox. AISI 316L Posi ción Descri pción 1 EQUIPO DE BOMBEO PARA AGUA NEBULIZADA. TUBERÍA HÚMEDA ENTRADA ALIMENTACIÓN RED MUNICIPAL RIESGO Nº2 A SISTEMA 2 24 V PANEL CONTROL 220/380 3N 50Hz SISTEMA ON INVERSIÓN FASES SEÑAL DE ACTUACIÓN BOMBA EN FUNCIONAMIENTO SEÑAL CONFIRMACIÓN EXTINCIÓN NIVEL DEPÓSITO BAJO CENTRALITA
0 Fire Extinguishing Systems Wet System with Selector Valves 6 Cabezal cerrado 5 Válvula by-pass 4 Válvula direccional 3 Cabezal abierto 2 Detector 1 Tubería acero inox. AISI 316L Posi ción Descri pción 1 RIESGO Nº3 6 RIESGO Nº2 EQUIPO DE BOMBEO PARA AGUA NEBULIZADA. TUBERÍA HÚMEDA CON VÁLVULAS DIRECCIONALES 4 5 ENTRADA ALIMENTACIÓN RED MUNICIPAL A SISTEMA RIESGO Nº1 SEÑAL DE ACTUACIÓN SISTEMA ON 24 V PANEL CONTROL 220/380 3N 50Hz INVERSIÓN FASES AVERÍA BOMBA EN FUNCIONAMIENTO SEÑAL CONFIRMACIÓN EXTINCIÓN NIVEL DEPÓSITO BAJO CENTRALITA 2 3 SEÑAL DETECTORES RIESGO Nº1 SEÑAL DETECTORES RIESGO Nº2
0 Fire Extinguishing Systems Pre-action System 1 RIESGO Nº1 3 Cabezal cerrado 2 Detector 1 Tubería acero inox. AISI 316L Posi ción Descri pción EQUIPO DE BOMBEO PARA AGUA NEBULIZADA. ACCIÓN PREVIA ENTRADA ALIMENTACIÓN RED MUNICIPAL RIESGO Nº2 A SISTEMA 24 V PANEL CONTROL 3N 220/380 50Hz 24 V SEÑAL DE ACTUACIÓN SISTEMA ON INVERSIÓN FASES AVERÍA BOMBA EN FUNCIONAMIENTO SEÑAL CONFIRMACIÓN EXTINCIÓN NIVEL DEPÓSITO BAJO CENTRALITA SEÑAL DE DETECTORES 2 3 SEÑAL DETECTORES RIESGO Nº1 Y Nº2